Cantec Systems - Battery Service and Maintenance Program
Battery Service and Maintenance Program
Contact Cantec Systems Service Group for detailed information on our complete Turnkey DC Power Installation and Battery Assurance Program.

Solving the Power System Puzzle
At one time or another, we've all experienced the need for battery backup. Remember the last time a storm knocked out the power in your home and you reached for a flashlight, only to find the batteries dead? Stationary batteries need maintenance to perform in times of emergency, too. That's why Cantec Systems Service Group has developed the most comprehensive Stationary Battery Maintenance Program in the industry today.
Contact Cantec Systems Service Group for detailed information on our complete Turnkey DC Power Installation and Battery Assurance Program.
Powerful Batteries Need Powerful Backup
Cantec Systems Service Group Battery Assurance Program can be designed to fit any application-Telecommunications, UPS, Utilities and Switchgear. Our exclusive Planned Maintenance Inspections assure that your system delivers maximum power when you need it.
Planned Maintenance Agreements to Suit Your Needs
Each of our maintenance programs offer over 15 vitally important measurements and inspections which can be tailored to meet individual site or customer requirements. Cantec Systems performs all maintenance procedures recommended per IEEE standard 450. This includes all voltage, resistance, specific gravity, current and temperature measurements, a complete visual inspection, and a professional report summarizing the results. Cantec Systems will also work with you on any recommended course of action that may be necessary to insure proper operation of your investment.
Cantec Systems Service Planned Maintenance Program
Cantec Systems can perform a complete Planned Maintenance Program that follows IEEE standard 450 recommendations, or customize the program to meet your needs. Cantec Systems offers two levels of Planned Maintenance:
- Basic Care: Cantec Systems will perform all quarterly and annual maintenance as required by IEEE standard 450. All monthly measurements and inspections are the customer's responsibility.
- Total Care: Cantec Systems will handle the total maintenance package, performing all monthly, quarterly, and annual maintenance procedures following IEEE standard 450.
- Custom Care: Cantec Systems will work with you to come up with a maintenance program specific to your unique needs.
- Safety & Spill Containment: Cantec Systems offers the only patented, UL-listed, NEBS-approved spill containment system on the market. This system uses durable designs built from quality materials and a proprietary non-gassing pillow system to quickly absorb and neutralize electrolyte in a manner that allows proper disposal.
- Load Testing: Cantec Systems offers a full range of load testing options to accurately determine the state of health of any battery system We utilize forced air DC load banks to determine the exact capacity of any system. Our load testing procedures are based on the IEEE 450 and practices recommended by major battery manufacturers.
Contact Cantec Systems Service Group for detailed information on our complete Turnkey DC Power Installation and Battery Assurance Program.
Total Maintenance Care Program Details
| Program Features | Monthly | Quarterly | Annually |
|---|---|---|---|
| Measure and record battery voltage |
|
|
|
| Measure and record charger output current and voltage |
|
|
|
| Measure and record ambient temperature |
|
|
|
| Inspect electrolyte levels and add water as required |
|
|
|
| Measure and record pilot cell float voltage, specific gravity and electrolyte temperature |
|
|
|
| Inspect battery, rack, and battery area and clean as necessary |
|
|
|
| Inspect for cracks in cells, leakage, and terminal or rack corrosion |
|
|
|
| Measure and record the specific gravity of each cell |
|
|
|
| Measure and record the voltage of each cell/unit |
|
|
|
| Measure and record the total voltage of the system |
|
|
|
| Measure and record the electrolyte temperature of every sixth cell/unit |
|
|
|
| Visually inspect each cell/unit in detail |
|
|
|
| Visually inspect each connection |
|
|
|
| Measure and record 100% of connection resistances |
|
|
|
| Measure and record torque values of each connection |
|
|
|
| Inspect the integrity of the battery rack |
|
|
|
| Record date of cleaning and inspection |
|
|
|
| Provide inspection report |
|
|
|
The Cantec Systems Service Difference
The Cantec Systems Service Group goes beyond offering a complete Stationary Maintenance program as recommended per IEEE standards. Cantec Systems also offers the following services as part of our everyday customer support.
- 90 day warranty on all parts and labour
- Call us for emergency service response
Contact Cantec Systems Service Group for detailed information on our complete Turnkey DC Power Installation and Battery Assurance Program.